I’m surprised that some companies discourage the use of shaft brushes because—they claim—conditions calling for these brushes don’t exist. If I were in a mischievous mood, I might say dissemination of such information could be considered a positive by the motor-repair industry. After all, bearing replacement is simple and lucrative (LOL). But I’m really not feeling mischievous about this topic.
Capacitive coupling and resulting shaft voltages and currents exist in all induction machines. It’s part of the reason why very large machines (over 1000 Volts) will have insulated opposite drive-end bearings and grounded drive-end bearings. The amount of voltage is considerably higher than in a low voltage (<1000 Volt) machine that is operating on a sinusoidal voltage. The amount of energy isn’t great enough, in the smaller machines, to discharge across bearing surfaces, in a majority of cases. However, in pulse-width modulated variable-frequency-drive (VFD) applications, the high carrier frequency (pulses) and resulting wave-shapes induce a voltage and resulting current into the shaft.
On smaller motors—those under 100 hp—you can ground the drive-end shaft and reduce the current to a manageable level. On units over 100 hp, you usually have to insulate the opposite drive end and ground it with a shaft brush in order to re-direct and reduce shaft currents. The reason for this is to prevent circulating currents from damaging the bearings in the driven equipment (something that could happen if you only insulate the bearings).
It’s true that shaft voltages and currents will not always reach levels that are high enough to rapidly degrade bearings in all VFD applications. There are typically several options for determining if this is going to be an issue: Your first option is to allow the motor to operate and fail, then address the issue and install shaft brushes after that or a subsequent failure. The second option is to install shaft brushes and insulated bearings on all VFD-operated machines. Your last option is to let a service company test for shaft voltage.
Shaft voltages can’t be detected with a multi-meter unless they are extremely severe. Rather, it requires an oscilloscope of 100 MHz or greater, preferably 200-300MHz. In analyzing the voltage, note values of 20-120+ Volts peak-to-peak for common mode voltage, and discharge patterns ranging from 6 volts to 80+ Volts peak. They point to issues that MUST be addressed. MT
Howard Penrose is VP of Engineering and Reliability Services for Dreisilker Electric Motors, Webmaster of IEEE’s Dielectrics and Electrical Insulation Society, and Director of Outreach for SMRP. Email: This e-mail address is being protected from spambots. You need JavaScript enabled to view it .
WIRELESS TEST TOOLS CAN CUT TROUBLESHOOTING TIMEBy: Fluke Corporation
The automation of more and more processes and operations in today’s factories and commercial buildings is helping to reduce energy consumption and increase safety and productivity as never before. However, automation has also added a large dose ofcomplexity for the technicians who maintain and troubleshoot the systems. Click here to learn how Fluke's CNX 3000 Wireless system can help.

New Pig’s PIG® Latching Drum Lids enable quick, easy drum access and secure closure to help meet closed container regulations. Designed to open and close easily with one hand, the Lids keep drum contents dry and pure without hassle.
A partnership with Maintenance Technology and Lubrication Management & Technology keeps your message, products and services in front of 82,000+ decision-makers 24/7/365.
Online, in print and in person, our two synergistic publications are better than one. For more information, click here to contact your MT/LMT Sales Representative today.