Solution Spotlight: When VFDs Can't Detect A Ground Fault

02solution

You may be putting your personnel and motors at risk.

Driven by concerns over arc-flash hazards, more plants are converting to high-resistance ground (HRG) electrical systems.

Unfortunately, many maintenance managers don't realize that that the ground-fault protection built into their variable frequency drives (VFDs) won't work with a high-resistance grounded system. They assume their personnel and motors are protected, when in truth they may be placing both at risk.

HRG limits ground-fault current and prevents a phase-to-ground condition from escalating to an arcing fault. Many VFDs are designed for use with solidly grounded systems—where large ground-fault currents are possible. Typically, a VFD's on-board ground-fault protection is set to trip at a high value, such as 50% of full load. In an HRG system, however, the ground-fault current will never reach the 50% set point. Consequently, a ground fault may go undetected and cause costly damage to the drive and motor.

Littelfuse engineers noticed this problem after investigating a situation at a refinery that had suffered damage to a low-voltage motor. Their research revealed that 29 of 30 popular-brand VFDs appeared to have ground-fault protection incompatible with HGR systems.

For the refinery, the solution was to install PGR-5701 Ground-Fault Relays from Littelfuse. The PGR-5701 is a microprocessor-based ground-fault relay compatible with solidly and resistance-grounded systems. It can detect a ground fault across the commonly used variable-frequency range of a VFD, and can—thanks to advanced digital filtering technology—work reliably in the presence of considerable harmonic noise. The output contacts can be connected to an alarm system, such as a PLC, can be connected to stop the VFD or trip an upstream circuit-interrupting device. Properly located, the relay can detect a ground fault in the VFD and downstream (load side) of the VFD.

Beyond detecting fault current, the relay can reveal leakage currents as they develop. Motor insulation can be damaged due to moisture, vibration, chemicals and dust. A sensitive ground-fault relay with advanced filtering will detect insulation breakdown at an early stage without nuisance tripping. In fact, the PGR-5701 relay acts as a preventive-maintenance device, alerting operators to a problem before equipment is severely damaged. This could save thousands of dollars in downtime, replacement parts and liability lawsuits.

Littelfuse
Chicago, IL

For more info, enter 30 at www.MT-freeinfo.com

Newsletter Sign Up



Your First Name:

Your Last Name:

Your E-Mail Address:

Would you like our Newsletter?:

Enter verification image value
  

Featured White Paper

fluke-white-paper-aprilWIRELESS TEST TOOLS CAN CUT TROUBLESHOOTING TIME

By: Fluke Corporation

The automation of more and more processes and operations in today’s factories and commercial buildings is helping to reduce energy consumption and increase safety and productivity as never before. However, automation has also added a large dose ofcomplexity for the technicians who maintain and troubleshoot the systems. Click here to learn how Fluke's CNX 3000 Wireless system can help. 

Featured Supplier: New Pig

newpig

New Pig’s PIG® Latching Drum Lids enable quick, easy drum access and secure closure to help meet closed container regulations. Designed to open and close easily with one hand, the Lids keep drum contents dry and pure without hassle.

Click here to see PIG Latching Drum Lids in action.

Connect with MT


linkedin
 

facebook   twitter

 Follow Maintenance Technology for the latest updates, news and more.

Synergy Is In Our DNA

A partnership with Maintenance Technology and Lubrication Management & Technology keeps your message, products and services in front of 82,000+ decision-makers 24/7/365.

Online, in print and in person, our two synergistic publications are better than one. For more information, click here to contact your MT/LMT Sales Representative today.