Electrical-Safety Sense: Confusing Fusing Issue

Fusing a panel-mount voltage indicator ensures an electrically secure installation as per NEC, but it simultaneously decreases electrical safety as per NFPA 70E. The reason for this is the propensity of false negative readings from the voltage detector as a result of the over-current protection.

What’s an electrical-safety-conscious company using a voltage indicator to do when it’s confronted with the “to-fuse-or-not-to-fuse” question? Even Shakespeare’s Hamlet would rightly conclude that the only safe course of action would be “not to fuse.”

A permanent electrical-safety device like a voltage indicator has one full-time job: to indicate voltage. A blown fuse on its input creates a false negative indication of voltage which, if trusted, is a hazard.

A fuse also adds four connection points of failure for each phase. In electrical safety, once you touch a live conduction, there’s always an electric incident—because electrical energy is, after all, instantaneous. Thus, it’s crucial to avoid any chance of potentially precarious false negative readings. 

NFPA 70E—as well as the logic of safety—recognized that there are varying degrees between “a risk” and a “greater risk,” so it astutely included a “Hazard Risk Procedure” in Annex F. The same principle, as stated below, allows for energized work, which is a risk if de-energizing the system is a greater risk.

“Greater Hazard. Energized work shall be permitted where the employer can demonstrate that de-energizing introduces additional or increased hazards.” …NFPA 70E 130.1(A)(1)

Similar statements exist in the NEC, which allows for un-fused conductors if a blown fuse creates a greater hazard:

“…for example, the control circuit of a fire-pump motor and the like.” …NEC 430.72

Including over-current protection for a voltage indicator installation increases the opportunity for a false negative reading, thereby creating a greater hazard than the risk posed by an un-fused conductor. MT

To learn more about specific recommendations and practices, visit: info.graceport.com/fusing; or email the author: This e-mail address is being protected from spambots. You need JavaScript enabled to view it .

Newsletter Sign Up



Your First Name:

Your Last Name:

Your E-Mail Address:

Would you like our Newsletter?:

Enter verification image value
  

Featured White Paper

fluke-white-paper-aprilWIRELESS TEST TOOLS CAN CUT TROUBLESHOOTING TIME

By: Fluke Corporation

The automation of more and more processes and operations in today’s factories and commercial buildings is helping to reduce energy consumption and increase safety and productivity as never before. However, automation has also added a large dose ofcomplexity for the technicians who maintain and troubleshoot the systems. Click here to learn how Fluke's CNX 3000 Wireless system can help. 

Featured Supplier: New Pig

newpig

New Pig’s PIG® Latching Drum Lids enable quick, easy drum access and secure closure to help meet closed container regulations. Designed to open and close easily with one hand, the Lids keep drum contents dry and pure without hassle.

Click here to see PIG Latching Drum Lids in action.

Do you control your maintenance, or is it controlling you?

Are you struggling with a high ratio of emergency (unplanned) to planned work orders, a huge backlog, a lack of sufficient resources, an inability to balance the work load, constant work interruptions, not having parts when needed, recurring failures, and much more. In these lean times, when more is expected from fewer resources, having a highly efficient maintenance program with thoughtful planning and scheduling is the key to success.  

This white paper will help you reduce maintenance costs and maximize efficiencyClick here to download the White Paper.