Electrical-Safety Sense: PESDs Meet And Exceed NFPA 70E 120.1

An electrical-safety program is safer when workers can determine a zero-electrical-energy state without exposing themselves to voltage. Article 120.1(1)–(6) provides a six-step procedure for creating an electrically safe work condition.  Here is a portion of the steps:

  • 120.1(1) Identify all sources of electrical energy.
  • 120.1(3) If possible, visually verify the isolator blades.
  • 120.1(5) Use an adequately rated voltage detector.
  • 120.1(5) Physically contact the voltage source.
  • 120.1(5) Checks voltage phase-phase-ground.
  • 120.1(5) Ensure the voltage detector functions before and after the procedure.

Permanent Electrical Safety Devices (PESDs) mounted to the outside of your control panel and wired to every voltage source entering your panel provide a way to verify and identify all sources of electrical energy without exposing workers to that energy (120.1). An illuminated 3-phase voltage indicator verifies the isolator blades of disconnects and circuit breakers while giving a visual indication outside the panel (120.3). The CAT III/IV rating of thru-door voltage indicators and non-contact voltage portals are adequately rated for use in power-distribution systems. Because both devices are physically wired to the voltage source, they meet the 120.1(5). A voltage indicator not only checks voltage phase-to-phase and phase-to-ground, but it performs this function every second of every minute of every day. When a non-contact voltage detector (NCVD) is used in conjunction with voltage portals, each device checks the other to ensure proper functionality before and after the procedure. Furthermore, the NCVD can be checked to another voltage source.

Voltmeters test voltage, then are put back in the tool belt, but a voltage indicator hardwired to the source voltage stays on the job and tests voltage all the time. It is like a lifeguard watching out for workers to make sure no voltage shows up during the work or task. It finds voltage so voltage doesn’t find you. MT

To learn more about specific recommendations and practices, email the author: This e-mail address is being protected from spambots. You need JavaScript enabled to view it .

For more info, enter 04 at www.MT-freeinfo.com

Sponsored Information

Newsletter Sign Up



Your First Name:

Your Last Name:

Your E-Mail Address:

Would you like our Newsletter?:

Enter verification image value
  

Featured White Paper

fluke-white-paper-aprilWIRELESS TEST TOOLS CAN CUT TROUBLESHOOTING TIME

By: Fluke Corporation

The automation of more and more processes and operations in today’s factories and commercial buildings is helping to reduce energy consumption and increase safety and productivity as never before. However, automation has also added a large dose ofcomplexity for the technicians who maintain and troubleshoot the systems. Click here to learn how Fluke's CNX 3000 Wireless system can help. 

Featured Supplier: New Pig

newpig

New Pig’s PIG® Latching Drum Lids enable quick, easy drum access and secure closure to help meet closed container regulations. Designed to open and close easily with one hand, the Lids keep drum contents dry and pure without hassle.

Click here to see PIG Latching Drum Lids in action.

Connect with MT


linkedin
 

facebook   twitter

 Follow Maintenance Technology for the latest updates, news and more.

Synergy Is In Our DNA

A partnership with Maintenance Technology and Lubrication Management & Technology keeps your message, products and services in front of 82,000+ decision-makers 24/7/365.

Online, in print and in person, our two synergistic publications are better than one. For more information, click here to contact your MT/LMT Sales Representative today.